2.3.1.27 LD0.EFHPTOC2 Non-directional ground-fault protection, high stage (2) –
50G-2
Table 30: LD0.EFHPTOC2 Non-directional ground-fault protection, high stage (2) – 50G-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.EFIPTOC2
4010 250.1 .Str.general PICKUP Stage pickup 1=Pickup
4011 250.11 .mcd
4012 250.12 .Op.general TRIP Stage trip 1=Trip
4013 250.13 .mcd
2.3.1.28 LD0.EFLPTOC1 Non-directional ground-fault protection low stage (1) –
51G-1
Table 31: LD0.EFLPTOC1 Non-directional ground-fault protection low stage (1) – 51G-1
BitA RegA IEC 61850 name SA name Description Values
LD0.EFLPTOC1
3008 188.00 .Str.general PICKUP Stage pickup 1=Pickup
3009 188.01 .mcd
3010 188.02 .Op.general TRIP Stage trip 1=Trip
3011 188.03 .mcd
2.3.1.29 LD0.ESMGAPC1 Emergency start-up (1) – 62EST-1
Table 32: LD0.ESMGAPC1 Emergency start-up (1) – 62EST-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.ESMGAPC1
2934 183.06 .Str.general ST_EMERG_ENA Emergency start 1=Start
2935 183.07 .mcd
2.3.1.30 LD0.FRPFRQ1 Frequency protection (1) – 81-1
Table 33: LD0.FRPFRQ1 Frequency protection (1) – 81-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.FRPTRC1
3024 189.00 .Str.general PICKUP Stage 1 pickup 1=Pickup
3025 189.01 .mcd
Table continues on next page
Section 2 1MAC252756-MB B
Modbus data mappings
30 REM615 ANSI
Point List Manual