2.3.1.47 LD0.MAPGAPC5 Multipurpose protection (5) – MAP-5
Table 50: LD0.MAPGAPC5 Multipurpose protection (5) – MAP-5
BitA
RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC5
3040 190.00 .Op.general TRIP Stage trip 1 = Trip
3041 190.01 .mcd
3042 190.02 .Str.general PICKUP Stage pickup 1 = Pickup
3043 190.03 .mcd
2.3.1.48 LD0.MAPGAPC6 Multipurpose protection (6) – MAP-6
Table 51: LD0.MAPGAPC6 Multipurpose protection (6) – MAP-6
BitA RegA IEC 61850 name SA name Description Values
LD0.MAPGAPC6
3044 190.04 .Op.general TRIP Stage trip 1 = Trip
3045 190.05 .mcd
3046 190.06 .Str.general PICKUP Stage pickup 1 = Pickup
3047 190.07 .mcd
2.3.1.49 LD0.MDSOPT1 Runtime counter for machines and devices (1) – OPTM-1
Table 52: LD0.MDSOPT1 Runtime counter for machines and devices (1) – OPTM-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.MDSOPT1
2876 179.12 .OpTmWrn.stVal Accum.op.time Warn. 1=Warning
2877 179.13 .mcd
2878 179.14 .OpTmAlm.stVal Accum.op.time Alarm 1=Alarm
2879 179.15 .mcd
Section 2 1MAC252756-MB B
Modbus data mappings
38 REM615 ANSI
Point List Manual