BitA RegA IEC 61850 name SA name Description Values
3562 222.10 .SPCSO6.stVal Input 6 0/1=Off/On
3563 222.11 .mcd
3564 222.12 .SPCSO7.stVal Input 7 0/1=Off/On
3565 222.13 .mcd
3566 222.14 .SPCSO8.stVal Input 8 0/1=Off/On
3567 222.15 .mcd
2.3.1.55 LD0.NSPTOV1 Negative-sequence overvoltage protection (1) – 47-1
Table 58: LD0.NSPTOV1 Negative-sequence overvoltage protection (1) – 47-1
BitA RegA IEC 61850 name SA name Description Values
LD0.NSPTOV1
2968 185.08 .Str.general PICKUP General pickup 1=Pickup
2969 185.09 .mcd
2970 185.10 .Str.phsA phsA pickup 1=Pickup
2971 185.11 .mcd
2972 185.12 .Str.phsB phsB pickup 1=Pickup
2973 185.13 .mcd
2974 185.14 .Str.phsC phsC pickup 1=Pickup
2975 185.15 .mcd
2976 186.00 .Op.general TRIP General trip 1=Trip
2977 186.01 .mcd
2.3.1.56 LD0.NSPTOV2 Negative-sequence overvoltage protection (2) – 47-2
Table 59: LD0.NSPTOV2 Negative-sequence overvoltage protection (2) – 47-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.NSPTOV2
4034 252.2 .Str.general PICKUP General pickup 1=Pickup
4035 252.3 .mcd
.Str.phsA phsA pickup 1=Pickup
.mcd
.Str.phsB phsB pickup 1=Pickup
.mcd
.Str.phsC phsC pickup 1=Pickup
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 41
Point List Manual