BitA RegA IEC 61850 name SA name Description Values
.mcd
4036 252.4 .Op.general TRIP General trip 1=Trip
4037 252.5 .mcd
2.3.1.57 LD0.OEPVPH1 Overexcitation protection (1) – 24-1
Table 60: LD0.OEPVPH1 Overexcitation protection (1) – 24-1
BitA RegA IEC 61850 name SA name Description Values
LD0.OEPVPH1
4038 252.6 .Str.general PICKUP Stage pickup 1=Pickup
4039 252.7 .mcd
4040 252.8 .Op.general TRIP Stage trip 1=Trip
4041 252.9 .mcd
2.3.1.58 LD0.OEPVPH2 Overexcitation protection (2) – 24-2
Table 61: LD0.OEPVPH2 Overexcitation protection (2) – 24-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.OEPVPH2
4042 252.1 .Str.general PICKUP Stage pickup 1=Pickup
4043 252.11 .mcd
4046 252.14 .Op.general TRIP Stage trip 1=Trip
4047 252.15 .mcd
2.3.1.59 LD0.PHHPTOC1 Three-phase non-directional overcurrent protection,
high stage (1) – 50P-1
Table 62: LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1) – 50P-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC1
4002 250.2 .Str.general PICKUP General pickup 1=Pickup
4003 250.3 .mcd
.Str.phsA phsA pickup 1=Pickup
.mcd
.Str.phsB phsB pickup 1=Pickup
.mcd
Table continues on next page
Section 2 1MAC252756-MB B
Modbus data mappings
42 REM615 ANSI