BitA RegA IEC 61850 name SA name Description Values
.Str.phsC phsC pickup 1=Pickup
.mcd
4004 250.4 .Op.general TRIP General trip 1=Trip
4005 250.5 .mcd
2.3.1.60 LD0.PHHPTOC2 Three-phase non-directional overcurrent protection,
high stage (2) – 50P-2
Table 63: LD0.PHHPTOC2 Three-phase non-directional overcurrent protection, high stage (2) – 50P-2
BitA RegA IEC 61850 name SA name Description Values
LD0.PHHPTOC2
4006 250.6 .Str.general PICKUP General pickup 1=Pickup
4007 250.7 .mcd
.Str.phsA phsA pickup 1=Pickup
.mcd
.Str.phsB phsB pickup 1=Pickup
.mcd
.Str.phsC phsC pickup 1=Pickup
.mcd
4008 250.8 .Op.general TRIP General trip 1=Trip
4009 250.9 .mcd
2.3.1.61 LD0.PHIPTOC1 Three-phase non-directional overcurrent protection,
instantaneous stage (1) – 50P-3
Table 64: LD0.PHIPTOC1 Three-phase non-directional overcurrent protection, instantaneous stage (1) – 50P-3
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHIPTOC1
2890 180.10 .Str.general PICKUP General pickup 1=Pickup
2891 180.11 .mcd
2892 180.12 .Str.phsA phsA pickup 1=Pickup
2893 180.13 .mcd
2894 180.14 .Str.phsB phsB pickup 1=Pickup
2895 180.15 .mcd
2896 181.00 .Str.phsC phsC pickup 1=Pickup
Table continues on next page