BitA RegA IEC 61850 name SA name Description Values
2897 181.01 .mcd
2898 181.02 .Op.general TRIP General trip 1=Trip
2899 181.03 .mcd
2.3.1.62 LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low
stage (1) – 51P-1
Table 65: LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1) – 51P-1
BitA RegA IEC 61850 name SA name Description Values
LD0.PHLPTOC1
2880 180.00 .Str.general PICKUP General pickup 1=Pickup
2881 180.01 .mcd
2882 180.02 .Str.phsA Phs A pickup 1=Pickup
2883 180.03 .mcd
2884 180.04 .Str.phsB Phs B pickup 1=Pickup
2885 180.05 .mcd
2886 180.06 .Str.phsC Phs C pickup 1=Pickup
2887 180.07 .mcd
2888 180.08 .Op.general TRIP General trip 1=Trip
2889 180.09 .mcd
2.3.1.63 LD0.PHPTOV1 Three-phase overvoltage protection (1) – 59-1
Table 66: LD0. PHPTOV1 Three-phase overvoltage protection (1) – 59-1
BitA
RegA IEC 61850 name SA name Description Values
LD0. PHPTOV1
4026 251.1 .Str.general PICKUP General pickup 1=Pickup
4027 251.11 .mcd
.Str.phsA phsA pickup 1=Pickup
.mcd
.Str.phsB phsB pickup 1=Pickup
.mcd
.Str.phsC phsC pickup 1=Pickup
.mcd
4028 251.12 .Op.general TRIP General trip 1=Trip
4029 251.13 .mcd
Section 2 1MAC252756-MB B