2.3.1.64 LD0.PHPTOV2 Three-phase overvoltage protection (2) – 59-2
Table 67: LD0. PHPTOV2 hree-phase overvoltage protection (2) – 59-2
BitA
RegA IEC 61850 name SA name Description Values
LD0. PHPTOV2
4030 251.14 .Str.general PICKUP General pickup 1=Pickup
4031 251.15 .mcd
.Str.phsA phsA pickup 1=Pickup
.mcd
.Str.phsB phsB pickup 1=Pickup
.mcd
.Str.phsC phsC pickup 1=Pickup
.mcd
4032 252 .Op.general TRIP General trip 1=Trip
4033 252.1 .mcd
2.3.1.65 LD0.PHPTUV1 Three-phase undervoltage protection (1) – 27-1
Table 68: LD0.PHPTUV1 Three-phase undervoltage protection (1) – 27-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHPTUV1
2958 184.14 .Str.general PICKUP General pickup 1=Pickup
2959 184.15 .mcd
2960 185.00 .Str.phsA phsA pickup 1=Pickup
2961 185.01 .mcd
2962 185.02 .Str.phsB phsB pickup 1=Pickup
2963 185.03 .mcd
2964 185.04 .Str.phsC phsC pickup 1=Pickup
2965 185.05 .mcd
2966 185.06 .Op.general TRIP General trip 1=Trip
2967 185.07 .mcd
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 45
Point List Manual