2.3.1.66 LD0.PHPTUV2 Three-phase undervoltage protection (2) – 27-2
Table 69: LD0.PHPTUV2 Three-phase undervoltage protection (2) – 27-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.PHPTUV2
4022 251.6 .Str.general PICKUP General pickup 1=Pickup
4023 251.7 .mcd
.Str.phsA phsA pickup 1=Pickup
.mcd
.Str.phsB phsB pickup 1=Pickup
.mcd
.Str.phsC phsC pickup 1=Pickup
.mcd
4024 251.8 .Op.general TRIP General trip 1=Trip
4025 251.9 .mcd
2.3.1.67 LD0.PREVPTOC1 Phase reversal protection (1) – 46R-1
Table 70: LD0.PREVPTOC1 Phase reversal protection (1) – 46R-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.PREVPTOC1
2926 182.14 .Str.general PICKUP Stage pickup 1=Pickup
2927 182.15 .mcd
2928 183.00 .Op.general TRIP Stage trip 1=Trip
2929 183.01 .mcd
2.3.1.68 LD0.PSPTUV1 Positive-sequence undervoltage protection (1) – 27PS
Table 71: LD0.PSPTUV1 Positive-sequence undervoltage protection (1) – 27PS
BitA
RegA IEC 61850 name SA name Description Values
LD0.PSPTUV1
2948 184.04 .Str.general PICKUP General pickup 1=Pickup
2949 184.05 .mcd
2950 184.06 .Str.phsA phsA pickup 1=Pickup
2951 184.07 .mcd
2952 184.08 .Str.phsB phsB pickup 1=Pickup
2953 184.09 .mcd
Table continues on next page
Section 2 1MAC252756-MB B