BitA RegA IEC 61850 name SA name Description Values
2954 184.10 .Str.phsC phsC pickup 1=Pickup
2955 184.11 .mcd
2956 184.12 .Op.general TRIP General trip 1=Trip
2957 184.13 .mcd
2.3.1.69 LD0.RESCMMXU1 Residual current measurement (1) – IG-1
Table 72: LD0.RESCMMXU1 Residual current measurement (1) – IG-1
BitA RegA IEC 61850 name SA name Description Values
LD0.RESCMMXU1
2760 172.08 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2761 172.09 .mcd
2762 172.10 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2763 172.11 .mcd
2.3.1.70 LD0.RESVMMXU1 Residual voltage measurement (1) – VG-1
Table 73: LD0.RESVMMXU1 Residual voltage measurement (1) – VG-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.RESVMMXU1
2764 172.12 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2765 172.13 .mcd
2766 172.14 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2767 172.15 .mcd
2.3.1.71 LD0.ROVPTOV1 Residual overvoltage protection (1) – 59G-1
Table 74: LD0.ROVPTOV1 Residual overvoltage protection (1) – 59G-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV1
4014 250.14 .Str.general PICKUP General pickup 1=Pickup
4015 250.14 .mcd
4016 251.0 .Op.general TRIP General trip 1=Trip
4017 251.1 .mcd
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 47
Point List Manual