2.3.1.72 LD0.ROVPTOV2 Residual overvoltage protection (2) – 59N-1
Table 75: LD0.ROVPTOV1 Residual overvoltage protection (1) – 59N-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.ROVPTOV1
4014 250.14 .Str.general PICKUP General pickup 1=Pickup
4015 250.15 .mcd
4016 251 .Op.general TRIP General trip 1=Trip
4017 251.1 .mcd
2.3.1.73 LD0.SEQSPVC1 Fuse failure protection (1) – 60-1
Table 76: LD0.SEQSPVC1 Fuse failure protection (1) – 60-1
BitA RegA IEC 61850 name SA name Description Values
LD0.SEQSPVC1
2940 183.12 .Str.general FUSEF_U Pickup 1=Pickup
2941 183.13 .mcd
2942 183.14 .Str3Ph.general FUSEF_3PH 3-phase pickup 1=Pickup
2943 183.15 .mcd
2.3.1.74 LD0.SPCGAPC2 Generic control point (16 pcs) (2) – SPC-2
Table 77: LD0.SPCGAPC2 Generic control point (16 pcs) (2) – SPC-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.SPCGAPC2
3632 227.00 .SPCS01.stVal Ouput state 1 0/1=Off/On
3633 227.01 .mcd
3634 227.02 .SPCS02.stVal Ouput state 2 0/1=Off/On
3635 227.03 .mcd
3636 227.04 .SPCS03.stVal Ouput state 3 0/1=Off/On
3637 227.05 .mcd
3638 227.06 .SPCS04.stVal Ouput state 4 0/1=Off/On
3639 227.07 .mcd
3640 227.08 .SPCS05.stVal Ouput state 5 0/1=Off/On
3641 227.09 .mcd
3642 227.10 .SPCS06.stVal Ouput state 6 0/1=Off/On
3643 227.11 .mcd
Table continues on next page
Section 2 1MAC252756-MB B
Modbus data mappings
48 REM615 ANSI
Point List Manual