BitA RegA IEC 61850 name SA name Description Values
3644 227.12 .SPCS07.stVal Ouput state 7 0/1=Off/On
3645 227.13 .mcd
3646 227.14 .SPCS08.stVal Ouput state 8 0/1=Off/On
3647 227.15 .mcd
3648 228.00 .SPCS09.stVal Ouput state 9 0/1=Off/On
3649 228.01 .mcd
3650 228.02 .SPCS10.stVal Ouput state 10 0/1=Off/On
3651 228.03 .mcd
3652 228.04 .SPCS11.stVal Ouput state 11 0/1=Off/On
3653 228.05 .mcd
3654 228.06 .SPCS12.stVal Ouput state 12 0/1=Off/On
3655 228.07 .mcd
3656 228.08 .SPCS13.stVal Ouput state 13 0/1=Off/On
3657 228.09 .mcd
3658 228.10 .SPCS14.stVal Ouput state 14 0/1=Off/On
3659 228.11 .mcd
3660 228.12 .SPCS15.stVal Ouput state 15 0/1=Off/On
3661 228.13 .mcd
3662 228.14 .SPCS16.stVal Ouput state 16 0/1=Off/On
3663 228.15 .mcd
2.3.1.75 LD0.SSCBR1 Circuit-breaker condition monitoring (1) – 52CM-1
Table 78: LD0.SSCBR1 Circuit-breaker condition monitoring (1) – 52CM-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.SSCBR1
2848 178.00 .OpnAlm.stVal TRV_T_OP_ALM Opn travel time alarm 1=Alarm
2849 178.01 .ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm
LD0.SSOPM1
2850 178.02 .SprChaAlm.stVal SPR_CHR_ALM Spring charge alarm 1=Alarm
LD0.SSCBR1
2851 178.03 .OpCntAlm.stVal OPR_ALM CB operations alarm 1=Alarm
2852 178.04 .OpCntLO.stVal OPR_LO CB operations lockout 1=Lockout
2853 178.05 .LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm
LD0.SSIGM1
2854 178.06 .InsAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 49
Point List Manual