BitA RegA IEC 61850 name SA name Description Values
2855 178.07 .InsBlk.stVal PRES_LO Low pressure lockout 1=Lockout
LD0.SSCBR1
2856 178.08 .APwrAlm.stVal IPOW_ALM Lyt alarm 1=Alarm
2857 178.09 .APwrLO.stVal IPOW_LO Lyt lockout 1=Lockout
2858 178.10 .RmnNumOpAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm
2.3.1.76 LD0.STTPMSU1 Motor start-up supervision (1) – 66/51LRS-1
Table 79: LD0.STTPMSU1 Motor start-up supervision (1) – 66/51LRS-1
BitA RegA IEC 61850 name SA name Description Values
LD0.STTPMSS1
2920 182.08 .Str.general MOT_START Startup in progress 1=In progress
2921 182.09 .mcd
2922 182.10 .Op.general OPR_IIT Thermal stress trip 1=Trip
2923 182.11 .mcd
LD0.STTPMRI1
2924 182.12 .Op.general OPR_STALL Stalling trip 1=Trip
2925 182.13 .mcd
2.3.1.77 LD0.TCSSCBR1 Trip circuit supervision (1) – TCM-1
Table 80: LD0.TCSSCBR1 Trip circuit supervision (1) – TCM-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR1
2780 173.12 .CircAlm.stVal ALARM Supervision alarm 1=Alarm
2781 173.13 .mcd
2.3.1.78 LD0.TCSSCBR2 Trip circuit supervision (2) – TCM-2
Table 81: LD0.TCSSCBR2 Trip circuit supervision (2) – TCM-2
BitA
RegA IEC 61850 name SA name Description Values
LD0.TCSSCBR2
2782 173.14 .CircAlm.stVal ALARM Supervision alarm 1=Alarm
2783 173.15 .mcd
Section 2 1MAC252756-MB B