2.3.1.79 LD0.TRPPTRC1 Master trip (1) – 86/94-1
Table 82: LD0.TRPPTRC1 Master trip (1) – 86/94-1
BitA
RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC1
2740 171.04 .Op.general - Op. input signal 1=Operate
2741 171.05 .mcd
2742 171.06 .Tr.general - Trip output signal 1=Trip
2743 171.07 .mcd
2.3.1.80 LD0.TRPPTRC2 Master trip (2) – 86/94-2
Table 83: LD0.TRPPTRC2 Master trip (2) – 86/94-2
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC2
2744 171.08 .Op.general - Op. input signal 1=Operate
2745 171.09 .mcd
2746 171.10 .Tr.general - Trip output signal 1=Trip
2747 171.11 .mcd
2.3.1.81 LD0.VMMXU1 Three-phase voltage measurement (1) – VA, VB, VC
Table 84: LD0.VMMXU1 Three-phase voltage measurement (1) – VA, VB, VC
BitA
RegA IEC 61850 name SA name Description Values
LD0.VMMXU1
2784 174.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
2785 174.01 .mcd
2786 174.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
2787 174.03 .mcd
2788 174.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
2789 174.05 .mcd
2790 174.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
2791 174.07 .mcd
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 51
Point List Manual