2.3.1.82 LD0.XAGGIO130 Physical I/O states (AIM card XA130)
Table 85: LD0.XAGGIO130 Physical I/O states (AIM card XA130)
BitA
RegA IEC 61850 name SA name Description Values
LD0.XAGGIO130
3280 205.00 .Ind1.stVal XA130-Input 1 State 0/1=Off/On
3281 205.01 .mcd
.mom-only Mom only alternative
3282 205.02 .Ind2.stVal XA130-Input 2 State 0/1=Off/On
3283 205.03 .mcd
.mom-only Mom only alternative
3284 205.04 .Ind3.stVal XA130-Input 3 State 0/1=Off/On
3285 205.05 .mcd
.mom-only Mom only alternative
3286 205.06 .Ind4.stVal XA130-Input 4 State 0/1=Off/On
3287 205.07 .mcd
.mom-only Mom only alternative
2.3.1.83 LD0.XBGGIO110 Physical I/O states (BIO card XB110)
Table 86: LD0.XBGGIO110 Physical I/O states (BIO card XB110)
BitA
RegA IEC 61850 name SA name Description Values
LD0.XBGGIO110
3216 201.00 .Ind1.stVal X110-Input 1 State 0/1=Off/On
3217 201.01 .mcd
.mom-only Mom only alternative
3218 201.02 .Ind2.stVal X110-Input 2 State 0/1=Off/On
3219 201.03 .mcd
.mom-only Mom only alternative
3220 201.04 .Ind3.stVal X110-Input 3 State 0/1=Off/On
3221 201.05 .mcd
.mom-only Mom only alternative
3222 201.06 .Ind4.stVal X110-Input 4 State 0/1=Off/On
3223 201.07 .mcd
.mom-only Mom only alternative
3224 201.08 .Ind5.stVal X110-Input 5 State 0/1=Off/On
3225 201.09 .mcd
Table continues on next page