2.3.1.88 LD0.XRGGIO130 Alarm/warning
Table 91: LD0.XRGGIO130 Alarm/warning
BitA
RegA IEC 61850 name SA name Description Values
LD0.XRGGIO130
3072 192.00 .Alm.stVal - XRGGIO130 Alarm 1=Alarm
3073 192.01 .mcd
3074 192.02 .Wrn.stVal - XRGGIO130 Warning 1=Warning
3075 192.03 .mcd
2.3.2 Unmapped indications
Unmapped indications are indication data that have no initial Modbus mapping locations,
but can be added to the user-definable Modbus area using the Communication
Management tool in PCM600. If Modbus events are enabled for these indication signals,
the event identification is the user-definable area address.
2.3.2.1 All premapped three-phase protection function stages, trip/phase-
dependent objects added
Table 92: All premapped three-phase protection function stages, trip/phase-dependent objects added
BitA
RegA IEC 61850 name SA name Description Values
LD0.xxxxxxxx (various)
.Op.phsA Phs A trip 1 = Trip
.mcd
.Op.phsB Phs B trip 1 = Trip
.mcd
.Op.phsC Phs C trip 1 = Trip
.mcd
2.3.2.2 Common data 2
Table 93: Common data 2
BitA
RegA IEC 61850 name SA name Description Values
LD0.LDEV1
.StLstOv.stVal Internal ind. overflow 1=Overflow
.mcd
.MeasLstOv.stVal Internal meas. overflow 1=Overflow
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 57
Point List Manual