BitA RegA IEC 61850 name SA name Description Values
.mcd
.ChgFlg.stVal Configuration changed 1=Changed
.mcd
.FacSet.stVal Factory settings in use 1=In use
.mcd
LD0.GNRLLTMS1
.TmChSt1.stVal Time synch. status 0/1=Down/Up
.mcd
LD0.SCHLCCH1
.ChLiv.stVal CH1LIV Ethernet channel 1 live 1=Live
.mcd
LD0.SCHLCCH2
.ChLiv.stVal CH2LIV Ethernet channel 2 live 1=Live
.mcd
LD0.SCHLCCH3
.ChLiv.stVal CH3LIV Ethernet channel 3 live 1=Live
.mcd
2.3.2.3 LD0.DIAGLCCH1 Ethernet supervision (1)
Table 94: LD0.DIAGLCCH1 Ethernet supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.DIAGLCCH1
.ChLiv.stVal CHLIV Ethernet channel live 1=Live
.mcd
.RedChLiv.stVal REDCHLIV Red. Ethernet channel live 1=Live
.mcd
2.3.2.4 LD0.IL1TCTR1 Three-phase CT supervision (1)
Table 95: LD0.IL1TCTR1 Three-phase CT supervision (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.IL1TCTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
Section 2 1MAC252756-MB B