2.3.2.25 LD0.TRPPTRC5 Master trip (5) – 86/94-5
Table 116: LD0.TRPPTRC5 Master trip (5) – 86/94-5
BitA
RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC5
.Op.general Op. input signal 1 = Operate
.mcd
.Tr.general Trip output signal 1 = Trip
.mcd
2.3.2.26 LD0.UL1TVTR1 Three-phase VT supervision (1)
Table 117: LD0.UL1TVTR1 Three-phase VT supervision (1)
BitA RegA IEC 61850 name SA name Description Values
LD0.UL1TVTR1
.Alm.stVal ALARM Alarm 1=Alarm
.mcd
.Wrn.stVal WARNING Warning 1=Warning
.mcd
2.3.2.27 LD0.XRGGIO130 Alarm/warning
Table 118: LD0.XRGGIO130 Alarm/warning
BitA
RegA IEC 61850 name SA name Description Values
LD0.XRGGIO130
.Alm.stVal - XRGGIO130 alarm 1=Alarm
.mcd
.Wrn.stVal - XRGGIO130 warning 1=Warning
.mcd
Section 2 1MAC252756-MB B
Modbus data mappings
66 REM615 ANSI
Point List Manual