2.4.1.12 Fault record structure header
Table 135: Fault record structure header
RegA
Type Scale IEC 61850 name SA name Description Values
Selection write
9401 i16 1 Read selection -99…3
Record data header
9402 u16 1 Record sequence num 0...65535
9403 u16 1 Unread records left 0...99
Timestamp of record
9404 u16 1 Year, month Year/Month
9405 u16 1 Day, hour Day/Hour
9406 u16 1 Minute, second Min/Sec
9407 u16 1 Millisecond Millisecond
9408 u16 1 Timestamp quality
2.4.1.13 Fault record data
The table shows all potential data available in the fault record application. Which data is
actually recorded depends on the functions available and enabled in the protection relay's
configuration.
Table 136: Fault record data
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.FLTRFRC1 Fault record data
9409 u32 1 .OpCnt.stVal Fault record number (high) 0..999999
9410 (Low word)
9411 i16 1 .ProFnc.stVal Protection function -32768...3276
7
9412 u16 100 .Hz.mag Frequency 30…80.00
[Hz]
9413 u16 100 .StrDur.mag Start duration 0...100.00 [%]
9414 u32 1000 .StrOpTm.mag Operate time [ms] (high) 0...999999.99
9
9415 (Low word)
9416 u32 100 .FltPtR.mag Fault resistance 0.00…
1000000.00
ohms
9417
(Low word)
Table continues on next page
Section 2 1MAC252756-MB B
Modbus data mappings
76 REM615 ANSI
Point List Manual