RegA Type Scale IEC 61850 name SA name Description Values
9418 u32 100 .FltDiskm.mag Fault distance 0.00…
9999.99 pu
9419 (Low word)
9420 u16 1 .ActSetGr.stVal Active setting group 1…6
9421 u16 1 .ShotPntr.stVal AR shot pointer value 0...7
Captured values during fault
9422 u16 1000 .Max50DifAA.mag Max. diff. current phs A 0.000...80.000
[pu]
9423 u16 1000 .Max50DifAB.mag Max. diff. current phs B 0.000...80.000
[pu]
9424 u16 1000 .Max50DifAC.mag Max. diff. current phs C 0.000...80.000
[pu]
9425 u16 1000 .Max50RstAA.mag Max. bias current phs A 0.000…
50.000 [pu]
9426 u16 1000 .Max50RstAB.mag Max. bias current phs B 0.000…
50.000 [pu]
9427 u16 1000 .Max50RstAC.mag Max. bias current phs C 0.000…
50.000 [pu]
9428 u16 1000 .DifAPhsA.mag Diff. current phs A 0.000...80.000
[pu]
9429 u16 1000 .DifAPhsB.mag Diff. current phs B 0.000...80.000
[pu]
9430 u16 1000 .DifAPhsC.mag Diff. current phs C 0.000...80.000
[pu]
9431 u16 1000 .RstAPhsA.mag Bias current phs A 0.000…
50.000 [pu]
9432 u16 1000 .RstAPhsB.mag Bias current phs B 0.000…
50.000 [pu]
9433 u16 1000 .RstAPhsC.mag Bias current phs C 0.000…
50.000 [pu]
9434 u16 1000 .DifARes.mag Diff. current Io 0.000...80.000
[pu]
9435 u16 1000 .RstARes.mag Bias current Io 0.000…
50.000 [pu]
9436 u16 1000 .Max50APhsA1.mag Max. current phs A(1) 0.000…
50.000 [×In]
9437 u16 1000 .Max50APhsB1.mag Max. current phs B(1) 0.000…
50.000 [×In]
9438 u16 1000 .Max50APhsC1.mag Max. current phs C(1) 0.000…
50.000 [×In]
9439 u16 1000 .Max50ARes1.mag Max. current Io(1) 0.000…
50.000 [×In]
9440 u16 1000 .APhsA1.mag Current phs A(1) 0.000…
50.000 [×In]
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 77
Point List Manual