RegA Type Scale IEC 61850 name SA name Description Values
9441 u16 1000 .APhsB1.mag Current phs B(1) 0.000…
50.000 [×In]
9442 u16 1000 .APhsC1.mag Current phs C(1) 0.000…
50.000 [×In]
9443 u16 1000 .ARes1.mag Current Io(1) 0.000…
50.000 [×In]
9444 u16 1000 .AResClc1.mag Current Io-Calc(1) 0.000…
50.000 [×In]
9445 u16 1000 .APsSeq1.mag Current Ps-Seq(1) 0.000…
50.000 [×In]
9446 u16 1000 .ANgSeq1.mag Current Ng-Seq(1) 0.000…
50.000 [×In]
9447 u16 1000 .PhVPhsA1.mag Voltage phs A(1) 0.000...4.000
[×Un]
9448 u16 1000 .PhVPhsB1.mag Voltage phs B(1) 0.000...4.000
[×Un]
9449 u16 1000 .PhVPhsC1.mag Voltage phs C(1) 0.000...4.000
[×Un]
9450 u16 1000 .PPVPhsAB1.mag Voltage phs AB(1) 0.000...4.000
[×Un]
9451 u16 1000 .PPVPhsBC1.mag Voltage phs BC(1) 0.000...4.000
[×Un]
9452 u16 1000 .PPVPhsCA1.mag Voltage phs CA(1) 0.000...4.000
[×Un]
9453 u16 1000 .VRes1.mag Voltage Uo(1) 0.000...4.000
[×Un]
9454 u16 1000 .VZro1.mag Voltage Zro-Seq(1) 0.000...4.000
[×Un]
9455 u16 1000 .VPsSeq1.mag Voltage Ps-Seq(1) 0.000...4.000
[×Un]
9456 u16 1000 .VNgSeq1.mag Voltage Ng-Seq(1) 0.000...4.000
[×Un]
9457 u16 100 .MaxTmpRl.mag PTTR thermal level 0.00...99.99
9458 u16 100 .AMaxNgPs.mag PDNSPTOC1 ratio I2/I1 0.00...999.99
[%]
9459 i16 100 .HzRteChg.mag Frequency gradient -10.00...10.00
[Hz/s]
9460 i16 100 .CondNeut.mag Conductance Yo -1000.00...10
00.00 [mS]
9461 i16 100 .SusNeut.mag Susceptance Yo -1000.00...10
00.00 [mS]
9462 i32 100 .PPLoopRis.mag Fault loop resistance -1000.00...10
00.00 [ohm]
9463 i32 (Low word)
Table continues on next page