2.4.1.18 SSR2 System status register (2) protection relay's mode and state
Table 141: SSR2 System status register (2) protection relay's mode and state
RegA
Type Scale IEC 61850 name SA name Description Values
129.00 Bit Device test mode 1=Test mode
129.01 Bit < reserved > 0
129.02 Bit Remote/Local state 0/1=Rem/Loc
Active setting group SG=1...6
129.03 Bit - bit 0
129.04 Bit - bit 1
129.05 Bit - bit 2
129.06 Bit
Protection relay's timesynch
failure 1=Failure
129.07 Bit < reserved > 0
129.08 Bit Last reset cause a 1=Cold start
129.09 Bit Last reset cause b 1=Watchdog
129.10 Bit Last reset cause c 1=Warm start
129.11 Bit < reserved > 0
129.12 Bit < reserved > 0
129.13 Bit < reserved > 0
129.14 Bit < reserved > 0
129.15 Bit < reserved > 0
2.4.1.19 SSR3 System status register (3) data available 1 (client-dependent)
Table 142: SSR3 System status register (3) data available 1 (client-dependent)
RegA
Type Scale IEC 61850 name SA name Description Values
130.00 Bit Unread event records available 1=Available
130.01 Bit Unread fault records available 1=Available
130.02 Bit < reserved > 0
130.03 Bit < reserved > 0
130.04 Bit Any momentary bit updated 1=Updated
130.05 Bit Any mcd bit set 1=Set
130.06 Bit Device restart bit 1=IED restart
130.07 Bit < reserved > 0
130.08 Bit Event record selected 1=Selected
130.09 Bit Fault record selected 1=Selected
130.10 Bit < reserved > 0
Table continues on next page
Section 2 1MAC252756-MB B
Modbus data mappings
82 REM615 ANSI
Point List Manual