2.4.1.29 LD0.CMMXU1 Phase current demand values (1) – IA, IB, IC
Table 152: LD0.CMMXU1 Phase current demand values (1) – IA, IB, IC
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.CAVMMXU1 Demand value
2001 u16 1000 .A.phsA.cVal.mag I_DMD_A Phs A amplitude 0.00…50.0
[xIn]
2002 u16 1000 .A.phsB.cVal.mag I_DMD_B Phs B amplitude 0.00…50.0
[xIn]
2003 u16 1000 .A.phsB.cVal.mag I_DMD_C Phs C amplitude 0.00…50.0
[xIn]
2004 Year - month
2005 Day - hour
2006 Minute - second
2007 Milliseconds
2008 Time quality
LD0.CMAMMXU1 Max demand values
2009 u16 1000 .A.phsA.cVal.mag Max demand IL1 Phs A amplitude 0.00…50.0
[xIn]
2010 Year - month
2011 Day - hour
2012 Minute - second
2013 Milliseconds
2014 Time quality
2015 u16 1000 .A.phsB.cVal.mag Max demand IL2 Phs B amplitude 0.00…50.0
[xIn]
2016 Year - month
2017 Day - hour
2018 Minute - second
2019 Milliseconds
2020 Time quality
2021 u16 1000 .A.phsC.cVal.mag Max demand IL2 Phs C amplitude 0.00…50.0
[xIn]
2022 Year - month
2023 Day - hour
2024 Minute - second
2025 Milliseconds
2026 Time quality
LD0.CMIMMXU1 Min demand values
Table continues on next page
1MAC252756-MB B Section 2
Modbus data mappings