RegA Type Scale IEC 61850 name SA name Description Values
u16 1000 .A.phsA.cVal.mag Max demand IL1 Phs A amplitude 0.00…50.0
[xIn]
u16 1000 .A.phsB.cVal.mag Max demand IL2 Phs B amplitude 0.00…50.0
[xIn]
u16 1000 .A.phsC.cVal.mag Max demand IL3 Phs C amplitude 0.00…50.0
[xIn]
2.4.1.30 LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
Table 153: LD0.CMMXU1 Three-phase current measurement (1) – IA, IB, IC
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMMXU1 Phase current (1)
138 u16 1000 .A.phsA.instCVal.mag I_INST_A Phs A amplitude
0.00...40.0
[xIn]
139 u16 1000 .A.phsB.instCVal.mag I_INST_B Phs B amplitude
0.00...40.0
[xIn]
140 u16 1000 .A.phsC.instCVal.mag I_INST_C Phs C amplitude
0.00...40.0
[xIn]
2.4.1.31 LD0.CSMSQI1 Sequence current measurement (1) – I1, I2, I0
Table 154: LD0.CSMSQI1 Sequence current measurement (1) – I1, I2, I0
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.CSMSQI1 Sequence of currents
143 u16 1000 .SeqA.c1.instCVal.mag I1_INST Positive amplitude
0.00...40.0
[xIn]
144 u16 1000 .SeqA.c2.instCVal.mag I2_INST Negative amplitude
0.00...40.0
[xIn]
145 u16 1000 .SeqA.c2.instCVal.mag I3_INST Zero amplitude
0.00...40.0
[xIn]
2.4.1.32 LD0.FMMXU1 Frequency measurement (1) – f-1
Table 155: LD0.FMMXU1 Frequency measurement (1) – f-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.FMMXU1
146 u16 100 .Hz.mag F_DB Frequency
35.00..75.00
[Hz]
Section 2 1MAC252756-MB B
Modbus data mappings
88 REM615 ANSI
Point List Manual

Table of Contents