2.4.1.33 LD0.MDSOPT1 Runtime counter for machines and devices (1) – OPTM-1
Since the register size is 16 bits, the value saturates at 65535 hours (approximately 7.5
years). Alternatively, a 32-bit user-definable register can be made of this data to cover the
whole 300 000 hours (34 years) range. The value can also, for example, be rescaled to
show “total operation days” instead by changing the scale factor from 1 to 1/24 = 0.0417.
Table 156: LD0.MDSOPT1 Runtime counter for machines and devices (1) – OPTM-1
RegA Type Scale IEC 61850 name SA name Description Values
LD0.MDSOPT1
2048 u16 1 .OpTmh.stVal OPR_TIME Total operation hours 0..299999
2.4.1.34 LD0.MPTTR1 Thermal overload protection for motors (1) – 49M-1
Table 157: LD0.MPTTR1 Thermal overload protection for motors (1) – 49M-1
RegA Type Scale IEC 61850 name SA name Description Values
LD0.MPTTR1
147 u16 1 .TmpRl.mag Therm-lev Thermal level 0.00...9.99
148 i16 1 .TmpUsed.mag TEMP_AMB Ambient temperature -99...999 [C]
149 u16 10 .ThmLevSt THERMLEV_ST Start therm.level 0.00...9.99
150 u16 10 .ThmLevEnd THERMLEV_END End therm.level 0.00...9.99
151 u16 1 .StrInhTms.stVal T_ENARESTART Est. time to reset block restart 0...99999 [s]
2.4.1.35 LD0.PEMMTR1 Three-phase energy measurements (1)
Table 158: LD0.PEMMTR1 Three-phase energy measurements (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.PEMMTR1
2040 u32 1 .SupWh.actVal Reverse active energy (high) 0..1E10 [kWh]
2041 .SupWh.actVal (low word)
2042 u32 1 .SupVArh.actVal Reverse reactive energy (high)
0..1E10
[kVArh]
2043 .SupVArh.actVal (low word)
2044 u32 1 .DemWh.actVal Forward active energy (high) 0..1E10 [kWh]
2045 .DemWh.actVal (low word)
2046 u32 1 .DemVArh.actVal Forward reactive energy (high)
0..1E10
[kVArh]
2047 .DemVArh.actVal (low word)
1MAC252756-MB B Section 2
Modbus data mappings
REM615 ANSI 89
Point List Manual