2.4.1.38 LD0.RESCMMXU1 Residual current demand value (1) – IG-1
Table 161: LD0.RESCMMXU1 Residual current demand value (1) – IG-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RCAVMMXU1 Demand value
1989 u16 1000 .A.res.cVal.mag I_DMD_RES Residual amplitude 0.00…50.0
[xIn]
1990 Year - month
1991 Day - hour
1992 Minute - second
1993 Milliseconds
1994 Time quality
LD0.RCMAMMXU1 Max. demand value
1995 u16 1000 .A.res.cVal.mag Max demand Io Residual amplitude 0.00…50.0
[xIn]
1996 Year - month
1997 Day - hour
1998 Minute - second
1999 Milliseconds
2000 Time quality
LD0.RCMIMMXU1 Min. demand value
u16 1000 .A.res.cVal.mag Min demand Io Residual amplitude 0.00…50.0
[xIn]
2.4.1.39 LD0.RESCMMXU1 Residual current measurement (1) – IG-1
Table 162: LD0.RESCMMXU1 Residual current measurement (1) – IG-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RESCMMXU1 Residual current (1)
141 u16 1000 .A.res.instCVal.mag I0_INST - amplitude
0.00...40.0
[xIn]
1MAC252756-MB B Section 2