2.4.1.40 LD0.RESVMMXU1 Residual voltage demand value (1) – VG-1
Table 163: LD0.RESVMMXU1 Residual voltage demand value (1) – VG-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RVAVMMXU1 Demand value
1977 u16 1000 .PhV.res.cVal.mag U_DMD_RES Residual amplitude 0.00…4.0
[xUn]
1978 Year - month
1979 Day - hour
1980 Minute - second
1981 Milliseconds
1982 Time quality
LD0.RVMAMMXU1 Max. demand value
1983 u16 1000 .PhV.res.cVal.mag Max demand Uo Residual amplitude 0.00…4.0
[xUn]
1984 Year - month
1985 Day - hour
1986 Minute - second
1987 Milliseconds
1988 Time quality
LD0.RVMIMMXU1 Min. demand value
u16 1000 .PhV.res.cVal.mag Min demand Io Residual amplitude 0.00…4.0
[xUn]
2.4.1.41 LD0.RESVMMXU1 Residual voltage measurement (1) – VG-1
Table 164: LD0.RESVMMXU1 Residual voltage measurement (1) – VG-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.RESVMMXU1 Residual voltage (1)
142 u16 1000 .A.res.instCVal.mag U0_INST - amplitude
0.00...4.00
[xUn]
2.4.1.42 LD0.SSCBR1 Circuit-breaker condition monitoring (1) – 52CM-1
Table 165: LD0.SSCBR1 Circuit-breaker condition monitoring (1) – 52CM-1
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.SSCBR1
2060 u16 1 .InaTmdCnt.stVal INA_DAYS CB inactive days 0...65535
2061 u16 1 .OpTmOpn.mag T_TRV_OP Open travel time 0...60000 [ms]
Table continues on next page
Section 2 1MAC252756-MB B
Modbus data mappings
92 REM615 ANSI
Point List Manual