created with the Application Configuration tool in PCM600. Standard configuration L is
not designed for using all the available functionality content in one protection relay at the
same time. To ensure the performance of the protection relay, the user specific
configuration load is verified with the Application Configuration tool of PCM600.
3.5.2 Functions
GUID-F1CB1DF2-9417-4121-BF2B-78A35A9AE94B V1 EN
Figure 109: Functionality overview for standard configuration L
3.5.2.1 Default I/O connections
Table 21: Default connections for analog inputs
Analog input
Description Connector pins
IA Phase A current X131:4-5
IB Phase B current X132:4-5
IC Phase C current X133:4-5
IG Residual current IG X130:1-2
Table continues on next page
Section 3 1MAC109016-MB C
REF615 standard configurations
100 REF615 ANSI
Application Manual