Analog input Description Connector pins
VA Phase voltage VA X131:7-8
VB Phase voltage VB X132:7-8
VC Phase voltage VC X133:7-8
Table 22: Default connections for binary inputs
Binary input Description Connector pins
BIO0005 BIO0007
X110-BI1 - X110:1-2 X110:1,5
X110-BI2 - X110:3-4 X110:2,5
X110-BI3 Circuit breaker open position indication X110:5-6 X110:3,5
X110-BI4 Circuit breaker closed position indication X110:7-6 X110:4-5
X110-BI5 - X110:8-9 X110:6,10
X110-BI6 - X110:10-9 X110:7,10
X110-BI7 - X110:11-12 X110:8,10
X110-BI8 - X110:13-12 X110:9-10
Table 23: Default connections for binary outputs
Binary output
Description Connector pins
X100-PO1 Close circuit breaker X100:6-7
X100-PO2 Circuit breaker failure protection trip to upstream breaker X100:8-9
X100-SO1 General pickup indication X100:10-11,(12)
X100-SO2 General trip indication X100:13-14
X100-PO3 Open circuit breaker/trip coil 1 X100:15-19
X100-PO4 Open circuit breaker/trip coil 2 X100:20-24
X110-SO1 Upstream overcurrent blocking X110:14-16
X110-SO2 Overcurrent trip alarm X110:17-19
X110-SO3 Ground-fault trip alarm X110:20-22
X110-SO4 Voltage protection trip alarm X110:23-24
X110-HSO1 Arc protection instance 1 trip activated X110:15-16
X110-HSO1 Arc protection instance 2 trip activated X110:19-20
X110-HSO1 Arc protection instance 3 trip activated X110:23-24