3.7 Standard configuration P
3.7.1 Applications
This standard configuration is mainly intended for single or double tie breaker control in
power distribution systems. With the directional phase and ground overcurrent, voltage
protection, synch check and power system metering, this configuration can be applied for
radial and loop feeders and intertie connections. In particular, this configuration provides
two sets of the remnant under voltage functions that can monitor two bus voltages with a
wide frequency range. As a result, it can be conveniently applied for automatic bus
transfer schemes.
The protection relay with a standard configuration is delivered from the factory with
default settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the protection relay enables this configuration to be
further adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.
3.7.2 Functions
GUID-EC38092D-A19C-4665-B7C0-9EAE328A17C4 V1 EN
Figure 224: Functionality overview for standard configuration P
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 165
Application Manual