3.7.3.2 Functional diagrams for disturbance recorder
The PICKUP and TRIP outputs from the protection stages are routed to trigger the
disturbance recorder or, alternatively, only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected signals from different
functions and the few binary inputs are also connected to the disturbance recorder.
RDRE1
O:80|T:2.5|I:1
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
C17
C18
C19
C20
C21
C22
C23
C24
C25
C26
C27
C28
C29
C30
C31
C32
C33
C34
C35
C36
C37
C38
C39
C40
C41
C42
C43
C44
C45
C46
C47
C48
C49
C50
C51
C52
C53
C54
C55
C56
C57
C58
C59
C60
C61
C62
C63
C64
TRIGGERED
CBXCBR1_52-1_EXE_CL
CBXCBR2_52-2_EXE_CL
TRPPTRC1_86_94-1_TRIP
CBXCBR1_52-1_EXE_OP
TRPPTRC2_86_94-2_TRIP
CBXCBR2_52-2_EXE_OP
CCBRBRF1_50BF-1_TRBU
CCBRBRF2_50BF-2_TRBU
PHPTUC1_37-1_TRIP
PHPTOV1_59-1_TRIP
PHPTOV2_59-2_TRIP
PHPTUV1_27-1_TRIP
PHPTUV2_27-2_TRIP
NSPTOV1_47-1_TRIP
NSPTOV2_47-2_TRIP
ROVPTOV2_59N-1_TRIP
ROVPTOV3_59N-2_TRIP
OC(1)_PICKUP_ALARM
ARCSARC1_AFD-1_ARC_FLT_DET
ARCSARC2_AFD-2_ARC_FLT_DET
ARCSARC3_AFD-3_ARC_FLT_DET
CCRDIF1_CCM_FAIL
GUID-778F90AC-D1B1-4BDF-AD13-007786F71D32 V1 EN
Figure 238: Disturbance recorder
Section 3 1MAC109016-MB C
REF615 standard configurations
182 REF615 ANSI
Application Manual