3.7.3.3 Functional diagrams for condition monitoring
Two trip circuit monitoring stages TCSSCBR1_TCM-1 and TCSSCBR2_TCM-2 are
provided to supervise the trip circuit of the circuit breaker connected at PO3 (X100:15-19)
and PO4 (X100:20-24).
TCSSCBR1
O:87|T:5|I:1
BLOCK ALARM
TCSSCBR2
O:52|T:5|I:2
BLOCK ALARM
NOT
O:82|T:2.5|I:0
IN OUT
OR
O:84|T:2.5|I:3
B1
B2
O
NOT
O:45|T:2.5|I:1
IN OUT
OR
O:49|T:2.5|I:5
B1
B2
O
CB2_POSITION_CLOSE
CB1_POSITION_CLOSE
TRPPTRC1_86_94-1_TRIP
TRPPTRC2_86_94-2_TRIP
TCSSCBR1_TCM1_ALARM
TCSSCBR2_TCM2_ALARM
GUID-9DCED52D-3641-451C-9C16-A9FCE08F4CDE V1 EN
Figure 239: Trip circuit monitoring
The TCSSCBR1_TCM-1 and TCSSCBR2_TCM-2 functions are blocked by
TRPPTRC1_86/94-1, TRPPTRC2_86/94-2 and when the circuit-breaker is not in closed
position.
By default it is expected that there is no external resistor in the circuit
breaker tripping/closing coil circuit connected parallel with circuit
breaker normally open/closed auxiliary contact.
The circuit breaker condition monitoring function SSCBR1_52CM supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision alarms.
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 183
Application Manual