Table 47: Auxiliary voltage supply
Terminal Description
X100:1 + Input
X100:2 - Input
5.1.3 Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch output
contacts, to trigger the digital fault recorder or for remote control of protection relay's
settings.
Binary inputs of slot X110 are available with configurations D, F, L, N and P.
Table 48: Binary input terminals X110:1-13 with BIO0005 module
Terminal Description
X110:1 BI1, +
X110:2 BI1, -
X110:3 BI2, +
X110:4 BI2, -
X110:5 BI3, +
X110:6 BI3, -
X110:6 BI4, -
X110:7 BI4, +
X110:8 BI5, +
X110:9 BI5, -
X110:9 BI6, -
X110:10 BI6, +
X110:11 BI7, +
X110:12 BI7, -
X110:12 BI8, -
X110:13 BI8, +
Table 49: Binary input terminals X110:1-10 with BIO0007 module
Terminal
Description
X110:1 BI1, +
X110:5 BI1, -
X110:2 BI2, +
X110:5 BI2, -
Table continues on next page
1MAC109016-MB C Section 5
Protection relay's physical connections
REF615 ANSI 203
Application Manual