Function IEC 61850 ANSI D F L N P
Minimum pulse timer (2 pcs) TPGAPC 62TP 4 4 4 4 4
Minimum pulse timer (2 pcs, second
resolution)
TPSGAPC 62TPS 1 1 1 1 1
Minimum pulse timer (2 pcs, minute
resolution)
TPMGAPC 62TPM 1 1 1 1 1
Pulse timer (8 pcs) PTGAPC 62PT 2 2 2 2 2
Time delay off (8 pcs) TOFGAPC 62TOF 4 4 4 4 4
Time delay on (8 pcs) TONGAPC 62TON 4 4 4 4 4
Set-reset (8 pcs) SRGAPC SR 4 4 4 4 4
Move (8 pcs) MVGAPC MV 2 2 2 2 2
Generic control point (16 pcs) SPCGAPC SPC 2 2 2 2 2
Analog value scaling SCA4GAPC SCA4 3 3 3 3 3
Integer value move MVI4GAPC MVI4 1 1 1 1 1
Generic up-down counters UDFCNT CTR 4 4 4 4 4
1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks
available in the standard configuration.
() = Optional
1) One of the following can be ordered as an option; Admittance based E/F, Wattmetric based E/F or Harmonics based E/F. The option is an addition
to the existing E/F of the original configuration. The optional ground-fault protection has a predefined configuration in the relay. The optional
ground-fault protection can be set on or off.
2) “Calculated V0” is always used
3) “Measured IG” is always used
4) Only available with IEC 61850-9-2
5) Master Trip included and connected to corresponding HSO in the configuration only when BIO0007 module is used. If additionally the ARC option
is selected, then AFD is connected in the configuration to the corresponding Master Trip input.
6) Power quality option includes Current total demand distortion, Voltage total harmonic distortion and Voltage variation.
7) Only available with COM0031...0037
3.1.1 Addition of control functions for primary devices and the use of
binary inputs and outputs
If extra control functions intended for controllable primary devices are added to the
configuration, additional binary inputs and/or outputs are needed to complement the
standard configuration.
If the number of inputs and/or outputs in a standard configuration is not sufficient, it is
possible either to modify the chosen standard configuration in order to release some
binary inputs or binary outputs which have originally been configured for other purposes,
or to integrate an external input/output module, for example RIO600, to the protection
relay.
The external I/O module’s binary inputs and outputs can be used for the less time-critical
binary signals of the application. The integration enables releasing some initially reserved
binary inputs and outputs of the protection relay’s standard configuration.
1MAC109016-MB C Section 3
REF615 standard configurations