TRPPTRC3
O:102|T:2.5|I:3
BLOCK
TRIP
RST_LKOUT
TRIP
CL_LKOUT
TRPPTRC4
O:99|T:2.5|I:4
BLOCK
TRIP
RST_LKOUT
TRIP
CL_LKOUT
TRPPTRC5
O:101|T:2.5|I:5
BLOCK
TRIP
RST_LKOUT
TRIP
CL_LKOUT
TRPPTRC3_86/94-3_TRIP
TRPPTRC4_86/94-4_TRIP
TRPPTRC5_86/94-5_TRIP
X120_BI4_RST_LOCKOUT
X120_BI4_RST_LOCKOUT
X120_BI4_RST_LOCKOUT
ARCSARC1_AFD-1_TRIP
ARCSARC2_AFD-2_TRIP
ARCSARC3_AFD-3_TRIP
GUID-DE0353C0-B5E5-4225-8B6A-F6428FECA254 V1 EN
Figure 28: Trip logic TRPPTRC3/4/5
3.3.3.2 Functional diagrams for disturbance recorder
The PICKUP and TRIP outputs from the protection stages are routed to trigger the
disturbance recorder or, alternatively, only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected signals from different
functions and the few binary inputs are also connected to the disturbance recorder.
Section 3 1MAC109016-MB C
REF615 standard configurations
56 REF615 ANSI
Application Manual