3.3.3.7 Functional diagrams for other functions
Protection
O:10|T:2.5|I:0
BI_SG_2
BI_SG_3
BI_SG_4
BI_SG_5
BI_SG_6
SG_LOGIC_SEL
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
BEH_TEST
BEH_BLK
NOT
O:35|T:2.5|I:0
IN OUT
Control
O:39|T:2.5|I:0
CTRL_OFF
CTRL_LOC
CTRL_STA
CTRL_REM
CTRL_ALL
OFF
LOCAL
STATION
REMOTE
ALL
BEH_TEST
BEH_BLK
NOT
O:38|T:2.5|I:4
IN OUT
TRUE
TRUE FALSE
CONTROL_LOCAL
CONTROL_REMOTE
GUID-36EC3158-6DEC-41C8-90B6-CC9561764A94 V1 EN
Figure 49: Functions for general logic states TRUE and FALSE, protection setting
group selection and local and remote control
Other functions include generic function blocks which are related to the relay only, for
example, local/remote switch, some generic functions related to logic TRUE or FALSE,
push button logic (valid for certain relay types) and so on.
3.3.3.8 Functional diagrams for other timer logics
The configuration also includes the overcurrent trip and ground-fault trip logic. The trip
logics are connected to the minimum pulse timer TPGAPC2 for setting the minimum
pulse length for the outputs. The output from TPGAPC2 is connected to binary outputs.
TPGAPC2
O:96|T:2.5|I:2
IN1
IN2
OUT1
OUT2
OR
O:95|T:2.5|I:16
B1
B2
O
OC_TRIP_PULSE
EF_TRIP_PULSE
EFLPTOC2_51N-1_TRIP
EFxPTOC_TRIP
PHxPTOC_TRIP
GUID-F47C320C-5F06-4585-A052-B4C3DDDFF606 V1 EN
Figure 50: Timer logic for overcurrent and ground-fault trip pulse
1MAC109016-MB C Section 3
REF615 standard configurations
REF615 ANSI 65
Application Manual