2.3.1.7 CTRL.Exxxxx1 Controllable earth switch (1)
Table 10: CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name SA name Description Values
CTRL.ESCILO1
.EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
.EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
.ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed
CTRL.ESCSWI1
.Pos.stSeld SELECTED CB selected 1=Selected
CTRL.ESXSWI1
.BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
.BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
2.3.1.8 CTRL.CCRDIF1 Current circuit failure protection
Table 11: CTRL.CCRDIF1 Current circuit failure protection
IEC 61850 name SA name Description Values
CTRL.CCRDIF1
.Alm.stVal FAIL Fail Alarm 1=Alarm
.Op.general ALARM Fail Operate 1=Operate
2.3.1.9 LD0.CMHAI1 Power quality - current total demand distortion
Table 12: LD0.CMHAI1 Power quality - current total demand distortion
IEC 61850 name
SA name Description Values
LD0.CMHAI1
.Alm.stVal ALARM Distortion alarm 10=Alarm
2.3.1.10 LD0.CMMXU1 Phase currents (1) limit supervision
Table 13: LD0.CMMXU1 Phase currents (1) limit supervision
IEC 61850 name
SA name Description Values
LD0.CMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
Section 2 1MRS756711 D
DNP3 data mappings
18 REF615
Point List Manual