2.3.1.11 LD0.DARREC1 Autorecloser
Table 14: LD0.DARREC1 Autorecloser
IEC 61850 name SA name Description Values
LD0.DARREC1
.PrgRec1.stVal INPRO_1 AR 1st reclose 1=In progress
.PrgRec2.stVal INPRO_2 AR 2nd reclose 1=In progress
.PrgRec3.stVal INPRO_3 AR 3rd reclose 1=In progress
.PrgRec4.stVal INPRO_4 AR 4th reclose 1=In progress
.PrgRec5.stVal INPRO_5 AR 5th reclose 1=In progress
.PrgRec.stVal INPRO AR in progress 1=In progress
.CBManCls.stVal MAN_CB_CL CB manually closed 1=CB closed
.LO.stVal LOCKED Lockout status 1=Lockout
.UnsRec.stVal UNSUC_RECL Reclose fail status 1=Failed
.InBlkThm.stVal - Thermal block (status) 1=Block
.RdyRec.stVal READY Ready reclose status 1=Ready
.ActRec.stVal ACTIVE Active reclose status 1=Active
.PrgDsr.stVal DISCR_INPRO Discrimination time in p. 1=In progress
.PrgCutOut.stVal CUTOUT_INPRO Cutout time in progress 1=In progress
.FrqOpAlm.stVal FRQ_OP_ALM Frequent operation alarm 1=Alarm
.RclTmStr.stVal - Reclaim time started 1=Started
.ProCrd.stVal - Protection coordination 1=In progress
.Op.general CLOSE_CB Operate (close XCBR) 1=Close CB
.OpOpn.general OPEN_CB Operate (open XCBR) 1=Open CB
.UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed
.WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal
2.3.1.12 LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1
Table 15: LD0.DEFHPDEF1 Directional earth-fault protection - high stage 1
IEC 61850 name
SA name Description Values
LD0.DEFHPTOC1 High stage (1)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
1MRS756711 D Section 2
DNP3 data mappings
REF615 19