2.3.1.21 LD0.EFLPTOC2 Non-directional earth-fault and sensitive earth-fault
protection - low stage 2
Table 24: LD0.EFLPTOC2 Non-directional earth-fault and sensitive earth-fault protection - low stage 2
IEC 61850 name SA name Description Values
LD0.EFLPTOC2 Low stage (2)
.Op.general OPERATE -Operate 1=Operate
.Str.general START -Start 1=Start
2.3.1.22 LD0.EFPADM1 Admittance-based earth-fault protection (1)
Table 25: LD0.EFPADM1 Admittance-based earth-fault protection (1)
IEC 61850 name SA name Description Values
LD0.EFPADM1
.Str.general START Stage1 start 1=Start
.Op.general OPERATE Stage1 operate 1=Operate
2.3.1.23 LD0.EFPADM2 Admittance-based earth-fault protection (2)
Table 26: LD0.EFPADM2 Admittance-based earth-fault protection (2)
IEC 61850 name
SA name Description Values
LD0.EFPADM2
.Str.general START Stage2 start 1=Start
.Op.general OPERATE Stage2 operate 1=Operate
2.3.1.24 LD0.EFPADM3 Admittance-based earth-fault protection (3)
Table 27: LD0.EFPADM3 Admittance-based earth-fault protection (3)
IEC 61850 name
SA name Description Values
LD0.EFPADM3
.Str.general START Stage3 start 1=Start
.Op.general OPERATE Stage3 operate 1=Operate
2.3.1.25 LD0.FRPFRQ1 Frequency protection (1)
Table 28: LD0.FRPFRQ1 Frequency protection (1)
IEC 61850 name
SA name Description Values
LD0.FRPTRC1
.Str.general START Stage start 1=Start
LD0.FRPTOF1 Overfrequency
Table continues on next page
Section 2 1MRS756711 D
DNP3 data mappings
22 REF615
Point List Manual