2.3.1.29 LD0.INPHAR1 Three-phase inrush detection
Table 32: LD0.INPHAR1 Three-phase inrush detection
IEC 61850 name SA name Description Values
LD0.INRPHAR1
.Str.general - General start 1=Start
2.3.1.30 LD0.INTRPTEF1 Transient/intermittent earth-fault protection
Table 33: LD0.INTRPTEF1 Transient/intermittent earth-fault protection
IEC 61850 name SA name Description Values
LD0.INTRPTEF1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.1.31 LD0.LEDGGIO1 LHMI LED indications
Table 34: LD0.LEDGGIO1 LHMI LED indications
IEC 61850 name
SA name Description Values
LD0.LEDGGIO1
.SPCSO1.stVal - LED 1 state 0/1=Off/On
.SPCSO2.stVal - LED 2 state 0/1=Off/On
.SPCSO3.stVal - LED 3 state 0/1=Off/On
.SPCSO4.stVal - LED 4 state 0/1=Off/On
.SPCSO5.stVal - LED 5 state 0/1=Off/On
.SPCSO6.stVal - LED 6 state 0/1=Off/On
.SPCSO7.stVal - LED 7 state 0/1=Off/On
.SPCSO8.stVal - LED 8 state 0/1=Off/On
.SPCSO9.stVal - LED 9 state 0/1=Off/On
.SPCSO10.stVal - LED 10 state 0/1=Off/On
.SPCSO11.stVal - LED 11 state 0/1=Off/On
2.3.1.32 LD0.LEDPTRC1 Global protection signals
Table 35: LD0.LEDPTRC1 Global protection signals
IEC 61850 name
SA name Description Values
LD0.LEDPTRC1 Global protection signals
.Op.general - -General Operate 1=Operate
.Op.phsA - -phsA Operate 1=Operate
.Op.phsB - -phsB Operate 1=Operate
Table continues on next page
Section 2 1MRS756711 D