2.3.1.50 LD0.PHPTUV3 Phase undervoltage protection - stage 3
Table 53: LD0.PHPTUV3 Phase undervoltage protection - stage 3
IEC 61850 name SA name Description Values
LD0.PHPTUV3
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.1.51 LD0.PSPTUV1 Positive-sequence undervoltage protection - stage 1
Table 54: LD0.PSPTUV1 Positive-sequence undervoltage protection - stage 1
IEC 61850 name SA name Description Values
LD0.PSPTUV1
.Op.general OPERATE Stage operate 1=Operate
.Str.general START Stage start 1=Start
2.3.1.52 LD0.PH1QVVR1 PQ - Voltage variation signals
Table 55: LD0.PH1QVVR1 PQ - Voltage variation signals
IEC 61850 name
SA name Description Values
LD0.PH1QVVR1
.VarStrGen.stVal - Variation event detected 1=Detected
.VarEnd.stVal - Variation event ended 1=Ended
.SwlOp.stVal - Swell event detected 1=Detected
.DipOp.stVal - Dip event detected 1=Detected
.IntrOp.stVal - Interruption event detected 1=Detected
2.3.1.53 DR.RDRE1 Disturbance recorder
Table 56: DR.RDRE1 Disturbance recorder
IEC 61850 name
SA name Description Values
DR.RDRE1
.RcdMade.stVal DR recording made 1=Made
2.3.1.54 LD0.RESCMMXU1 Residual current limit supervision
Table 57: LD0.RESCMMXU1 Residual current limit supervision
IEC 61850 name
SA name Description Values
LD0.RESCMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
1MRS756711 D Section 2
DNP3 data mappings
REF615 29
Point List Manual