2.3.1.55 LD0.RESVMMXU1 Residual voltage limit supervision
Table 58: LD0.RESVMMXU1 Residual voltage limit supervision
IEC 61850 name SA name Description Values
LD0.RESVMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
2.3.1.56 LD0.ROVPTOV1 Residual overvoltage protection (1)
Table 59: LD0.ROVPTOV1 Residual overvoltage protection (1)
IEC 61850 name SA name Description Values
LD0.ROVPTOV1
.Op.general OPERATE Stage 1 operate 1=Operate
.Str.general START Stage 1 start 1=Start
2.3.1.57 LD0.ROVPTOV2 Residual overvoltage protection (2)
Table 60: LD0.ROVPTOV2 Residual overvoltage protection (2)
IEC 61850 name
SA name Description Values
LD0.ROVPTOV2
.Op.general OPERATE Stage 2 operate 1=Operate
.Str.general START Stage 2 start 1=Start
2.3.1.58 LD0.ROVPTOV3 Residual overvoltage protection (3)
Table 61: LD0.ROVPTOV3 Residual overvoltage protection (3)
IEC 61850 name
SA name Description Values
LD0.ROVPTOV3
.Op.general OPERATE Stage 3 operate 1=Operate
.Str.general START Stage 3 start 1=Start
2.3.1.59 LD0.SECRSYN1 Synchrocheck
Table 62: LD0.SECRSYN1 Synchrocheck
IEC 61850 name
SA name Description Values
LD0.SECRSYN1
.SynPrg.stVal SYNC_INPRO Synch in progress 1=In progress
.FailCmd.stVal CMD_FAIL_AL CB close request failed 1=Failed
.FailSyn.stVal CL_FAIL_AL CB close command failed 1=Failed
Section 2 1MRS756711 D
DNP3 data mappings
30 REF615
Point List Manual