2.3.1.67 LD0.TRPPTRC2 Global conditioning (2)
Table 70: LD0.TRPPTRC2 Global conditioning (2)
IEC 61850 name SA name Description Values
.Op.general - Operate input signal 1=Operate
.Tr.general - Trip output signal 1=Trip
2.3.1.68 LD0.VMHAI1 PQ - Voltage total harmonic distortion
Table 71: LD0.VMHAI1 PQ - Voltage total harmonic distortion
IEC 61850 name SA name Description Values
LD0.VMHAI1
.Alm.stVal - Distortion alarm 1=Alarm
2.3.1.69 LD0.VMMXU1 Three-phase voltage limit supervision
Table 72: LD0.VMMXU1 Three-phase voltage limit supervision
IEC 61850 name SA name Description Values
LD0.VMMXU1
.HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
.HiWrn.stVal HIGH_WARN High warning 1=Warning
.LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
.LoWrn.stVal LOW_WARN Low warning 1=Warning
2.3.1.70 LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
Table 73: LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
IEC 61850 name
SA name Description Values
LD0.WPDSE1
.Str.general START Stage 1 start 1=Start
.Op.general OPERATE Stage 1 operate 1=Operate
2.3.1.71 LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
Table 74: LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
IEC 61850 name
SA name Description Values
LD0.WPDSE2
.Str.general START Stage 2 start 1=Start
.Op.general OPERATE Stage 2 operate 1=Operate
1MRS756711 D Section 2
DNP3 data mappings
REF615 33
Point List Manual