EasyManua.ls Logo

ABB Relion 615 series - LD0.WPWDE3 Wattmetric-Based Earth-Fault Protection (3); LD0.XAGGIO130 Physical I;O; LD0.XGGIO100 Physical I;O; LD0.XGGIO110 Physical I;O

ABB Relion 615 series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3.1.72 LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
Table 75: LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
IEC 61850 name SA name Description Values
LD0.WPDSE3
.Str.general START Stage 3 start 1=Start
.Op.general OPERATE Stage 3 operate 1=Operate
2.3.1.73 LD0.XAGGIO130 Physical I/O
Table 76: LD0.XAGGIO130 Physical I/O
IEC 61850 name SA name Description Values
LD0.XAGGIO130
.Ind1.stVal - X130-Input 1 1/0=ON/OFF
.Ind2.stVal - X130-Input 2 1/0=ON/OFF
.Ind3.stVal - X130-Input 3 1/0=ON/OFF
.Ind4.stVal - X130-Input 4 1/0=ON/OFF
2.3.1.74 LD0.XGGIO100 Physical I/O
Table 77: LD0.XGGIO100 Physical I/O
IEC 61850 name
SA name Description Values
LD0.XGGIO100
.SPCSO1.stVal - X100-Output 1 1/0=ON/OFF
.SPCSO2.stVal - X100-Output 2 1/0=ON/OFF
.SPCSO3.stVal - X100-Output 3 1/0=ON/OFF
.SPCSO4.stVal - X100-Output 4 1/0=ON/OFF
.SPCSO5.stVal - X100-Output 5 1/0=ON/OFF
.SPCSO6.stVal - X100-Output 6 1/0=ON/OFF
2.3.1.75 LD0.XGGIO110 Physical I/O
Table 78: LD0.XGGIO110 Physical I/O
IEC 61850 name
SA name Description Values
LD0.XGGIO110
.Ind1.stVal - X110-Input 1 1/0=ON/OFF
.Ind2.stVal - X110-Input 2 1/0=ON/OFF
.Ind3.stVal - X110-Input 3 1/0=ON/OFF
.Ind4.stVal - X110-Input 4 1/0=ON/OFF
.Ind5.stVal - X110-Input 5 1/0=ON/OFF
Table continues on next page
Section 2 1MRS756711 D
DNP3 data mappings
34 REF615
Point List Manual

Table of Contents

Other manuals for ABB Relion 615 series

Related product manuals