2.3.1.72 LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
Table 75: LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
IEC 61850 name SA name Description Values
LD0.WPDSE3
.Str.general START Stage 3 start 1=Start
.Op.general OPERATE Stage 3 operate 1=Operate
2.3.1.73 LD0.XAGGIO130 Physical I/O
Table 76: LD0.XAGGIO130 Physical I/O
IEC 61850 name SA name Description Values
LD0.XAGGIO130
.Ind1.stVal - X130-Input 1 1/0=ON/OFF
.Ind2.stVal - X130-Input 2 1/0=ON/OFF
.Ind3.stVal - X130-Input 3 1/0=ON/OFF
.Ind4.stVal - X130-Input 4 1/0=ON/OFF
2.3.1.74 LD0.XGGIO100 Physical I/O
Table 77: LD0.XGGIO100 Physical I/O
IEC 61850 name
SA name Description Values
LD0.XGGIO100
.SPCSO1.stVal - X100-Output 1 1/0=ON/OFF
.SPCSO2.stVal - X100-Output 2 1/0=ON/OFF
.SPCSO3.stVal - X100-Output 3 1/0=ON/OFF
.SPCSO4.stVal - X100-Output 4 1/0=ON/OFF
.SPCSO5.stVal - X100-Output 5 1/0=ON/OFF
.SPCSO6.stVal - X100-Output 6 1/0=ON/OFF
2.3.1.75 LD0.XGGIO110 Physical I/O
Table 78: LD0.XGGIO110 Physical I/O
IEC 61850 name
SA name Description Values
LD0.XGGIO110
.Ind1.stVal - X110-Input 1 1/0=ON/OFF
.Ind2.stVal - X110-Input 2 1/0=ON/OFF
.Ind3.stVal - X110-Input 3 1/0=ON/OFF
.Ind4.stVal - X110-Input 4 1/0=ON/OFF
.Ind5.stVal - X110-Input 5 1/0=ON/OFF
Table continues on next page
Section 2 1MRS756711 D
DNP3 data mappings
34 REF615