2.3.2.13 LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2)
Table 94: LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2)
IEC 61850 name SA name Description Type
.Rs1.ctlVal - Reset flip-flop 1 On
.Rs2.ctlVal - Reset flip-flop 2 On
.Rs3.ctlVal - Reset flip-flop 3 On
.Rs4.ctlVal - Reset flip-flop 4 On
.Rs5.ctlVal - Reset flip-flop 5 On
.Rs6.ctlVal - Reset flip-flop 6 On
.Rs7.ctlVal - Reset flip-flop 7 On
.Rs8.ctlVal - Reset flip-flop 8 On
2.3.2.14 LD0.SSCBR1 Reset signals of CB condition monitoring
Table 95: LD0.SSCBR1 Reset signals of CB condition monitoring
IEC 61850 name SA name Description Type
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy On
.RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter On
.RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm On
.RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm On
2.3.3 Analog inputs
Table 96: Explanations of the analog input table columns
Column name
Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible for example in ACT.
Description Short description of the signal. See the application function block documentation
for more details.
Values The value range of the original IEC 61850 data. Scaling is needed to convert
floating point data into DNP3 integer values.
S Scaling type selected as default. Default “R” means ratio scaling. See the DNP
communication protocol manual for details.
Arg 1, 2, 3, 4 Scaling argument values as default. When ratio scaling is selected, the four
values correspond to min value in, max value in, min value out, and max value
out. See the DNP communication protocol manual for details.
Section 2 1MRS756711 D
DNP3 data mappings
40 REF615
Point List Manual