2.3.3.11 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values
Table 107: CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.ESSXSWI2
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.12 CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position
values
Table 108: CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position values
IEC 61850 name SA name Description Values S Arg 1,2,3,4
CTRL.ESXSWI1
.Pos.stVal POSITION
Intermediate=0; Off=1; On=2;
Bad=3 0…3 R 0,3,0,3
2.3.3.13 LD0.DNPGGIO1 Active parameter setting group
Table 109: LD0.DNPGGIO1 Active parameter setting group
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.DNPGGIO1
.ActSG.stVal - Active setting group 1…6 R 1,6,1,6
2.3.3.14 LD0.FMMXU1 Frequency measurement
Table 110: LD0.FMMXU1 Frequency measurement
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.FMMXU1
.Hz.mag - Frequency value 35…75 [Hz] R 35,75,3500,7500
2.3.3.15 LD0.HAEFMHAI1 Current harmonics
Table 111: LD0.HAEFMHAI1 Current harmonics
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.HAEFMHAI
.HRmsA.res.cVal.mag - Current harmonics 0…250 [A] R 0,250,0,250
1MRS756711 D Section 2
DNP3 data mappings
REF615 43
Point List Manual