2.3.3.20 LD0.RESCMMXU1 Residual current (1)
Table 116: LD0.RESCMMXU1 Residual current (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.RESCMMXU1
.A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] R 0,40,0,4000
2.3.3.21 LD0.RESVMMXU1 Residual voltage (1)
Table 117: LD0.RESVMMXU1 Residual voltage (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.RESVMMXU1
.PhV.res.instCVal.mag U0_INST Residual voltage
0.00..4.00
[xUn] R 0,4,0,400
2.3.3.22 LD0.SECRSYN1 Synchrocheck line and bus state
Table 118: LD0.SECRSYN1 Synchrocheck line and bus state
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.SECRSYN1
.EnSt.stVal - Energization state 0…4 R 0,4,0,4
2.3.3.23 LD0.T1PTTR1 Temperature protection values (1)
Table 119: LD0.T1PTTR1 Temperature protection values (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.T1PTTR1
.Tmp.mag - Object temperature -100…9999.9 R -100,9999.9.0,-1000,99999
.TmpRl.mag - Relative temperature 0…99.9 R 0,99.9,0,999
2.3.3.24 LD0.VMMXU1 Voltage measurement
Table 120: LD0.VMMXU1 Voltage measurement
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.VMMXU1.PhV Phase-to-ground voltage
.phsA.cVal.mag U_DB_A -phsA magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsB.cVal.mag U_DB_B -phsB magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsC.cVal.mag U_DB_C -phsC magnitude
0.00…4.00
[xUn] R 0,4,0,400
Table continues on next page
1MRS756711 D Section 2
DNP3 data mappings
REF615 45
Point List Manual