• Raising frame
• Gasket
• Screws
Requirements for installation:
• Panel cut-out of 165.5 x 161.5 mm with mounting holes
• Depth behind the panel 103 mm
• When IP 54 degree of protection (according to IEC 60529) is required for the
front side, a gasket has to be used in the installation.
1. Mount the raising frame into the panel cut-out with four M4 screws.
A070589 V4 EN
Figure 9: Mounting the raising frame
A
173.5 ±0.3 mm 1 Panel
B 165.5 ±1 mm 2 Raising frame
C 161.5 ±1 mm 3 M4 screw
D 133 ±0.3 mm
E ∅ 5.5 mm
2. Loosen the four M5 fixing screws in the case to fit the case to the raising frame.
3. Mount the case to the raising frame.
1MRS756375 K Section 4
Mounting
615 series 23
Installation Manual