A071314 V4 EN
Figure 13: IED semi-flush mounted inclined
A 25 ° 1 M4 screws
B 221 mm 2 Gasket
C 9 mm 4 Case
D 107 mm 3 Angled frame
E 133 mm 5 Plug-in unit
F 230 mm
G 190 mm
4.3.5 Rack mounting the IED
A mounting kit is needed for rack mounting the IED. In addition to the detailed
mounting instructions, the 19" rack mounting kit includes:
• Mounting panel; the type of the mounting panel depends on the number of
mounted relays
• Screws
1. Mount the mounting panel to a 19" rack.
2. Loosen the four M5 fixing screws in the case to fit the case into the panel cut-
out.
3. Mount the case to the panel cut-out.
1MRS756375 K Section 4
Mounting
615 series 27
Installation Manual