A
B
C
A070592 V4 EN
Figure 17: Wall mounted IED
A
214 mm
B 177 mm
C 270 mm
Minimum of 50 mm space is needed between two kits.
When connecting the wires, a wall-mounted IED can be pulled out and turned 45°
(or 90°) degrees downwards or upwards.
To release the IED for pulling it out, push the locks beside the mounting frame.
To rotate the IED, loosen the knurled-head screws in the rails.
1MRS756375 K Section 4
Mounting
615 series 31
Installation Manual