REU615
Std. conf.
ANSI IEC
27/59
50P/51P
51P/51N
84M
90V
3U</3U>
3I>>>
3I/Io
TPOSM
COLTC
B
RET615
Std. conf.
ANSI IEC
27/59
49T
50L/50NL
50P/51P
51P/51N
87NL
87T
3U</3U>
3Ith>T
ARC
3I>>>
3I/Io
dIoLo>
3dI>T
E
3I (LV)
R
L
ClearESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
R
L
ClearESC
I
O
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
A
GUID-AB31C909-F38E-4885-AFEE-E2EEE3675263 V4 EN
Figure 12. Protection of a two-winding power transformer with RET615 standard configuration E
Figure 12 illustrates the protection of a two-winding power
transformer with RET615 standard configuration. The main
protection used in this application example is transformer
differential protection. Restricted earth-fault protection with
numerical low-impedance principle is applied on the
transformer's HV side. The RTD inputs of RET615 are utilized
for monitoring the oil temperature and oil level of the
transformer. Additionally, REU615 with the standard
configuration B is used as automatic voltage regulator for the
on-load tap changer of the transformer.
Transformer Protection and Control
1MRS756891 M
Product version: 5.0 FP1
ABB 17